§ 15A-4-103. Amendments to IBC applicable to City of Farmington.  


Latest version.
  •      The following amendments are adopted as amendments to the IBC for the City of Farmington:
    (1) A new IBC, Section (F) 903.2.13, is added as follows: "(F) 903.2.13 Group R, Division 3 Occupancies. An automatic sprinkler system shall be installed throughout every dwelling in accordance with NFPA 13D, when any of the following conditions are present:
    1. The structure is over two stories high, as defined by the building code;
    2. The nearest point of structure is more than 150 feet from the public way;
    3. The total floor area of all stories is over 5,000 square feet (excluding from the calculation the area of the basement and/or garage); or
    4. The structure is located on a street constructed after March 1, 2000, that has a gradient over 12% and, during fire department response, access to the structure will be gained by using such street. (If the access is intended to be from a direction where the steep gradient is not used, as determined by the Chief, this criteria shall not apply).
    Such sprinkler system shall be installed in basements, but need not be installed in garages, under eves or in enclosed attic spaces, unless required by the Chief."
    (2) A new IBC, Section 907.9, is added as follows: "907.9 Alarm Circuit Supervision. Alarm circuits in alarm systems provided for commercial uses (defined as other than one- and two-family dwellings and townhouses) shall have Class "A" type of supervision. Specifically, Type "B" or End-of-line resistor and horn supervised systems are not allowed."
    (3) In NFPA Section 13-07, new sections are added as follows: "6.8.6 FDC Security Locks Required. All Fire Department connections installed for fire sprinkler and standpipe systems shall have approved security locks.
    6.10 Fire Pump Disconnect Signs. When installing a fire pump, red plastic laminate signs shall be installed in the electrical service panel, if the pump is wired separately from the main disconnect. These signs shall state: "Fire Pump Disconnect ONLY" and "Main Breaker DOES NOT Shut Off Fire Pump".
    22.1.6 Plan Preparation Identification. All plans for fire sprinkler systems, except for manufacturer's cut sheets of equipment shall include the full name of the person who prepared the drawings. When the drawings are prepared by a registered professional engineer, the engineer's signature shall also be included.
    22.2.2.3 Verification of Water Supply:
    22.2.2.3.1 Fire Flow Tests. Fire flow tests for verification of water supply shall be conducted and witnessed for all applications other than residential unless directed otherwise by the Chief. For residential water supply, verification shall be determined by administrative procedure.
    22.2.2.3.2 Accurate and Verifiable Criteria. The design calculations and criteria shall include an accurate and verifiable water supply.
    24.2.3.7 Testing and Inspection of Systems. Testing and inspection of sprinkler systems shall include, but are not limited to:
    Commercial:
    FLUSH-Witness Underground Supply Flush;
    ROUGH Inspection-Installation of Riser, System Piping, Head Locations and all Components, Hydrostatic Pressure Test;
    FINAL Inspection-Head Installation and Escutcheons, Inspectors Test Location and Flow, Main Drain Flow, FDC Location and Escutcheon, Alarm Function, Spare Parts, Labeling of Components and Signage, System Completeness, Water Supply Pressure Verification, Evaluation of Any Unusual Parameter."
Enacted by Chapter 14, 2011 General Session