§ 15A-4-203. Amendments to IRC applicable to City of Farmington.  


Latest version.
  •      The following amendments are adopted as amendments to the IRC for the City of Farmington:
    (1) In IRC, R324 Automatic Sprinkler Systems, new IRC, Sections R324.1 and R324.2 are added as follows: "R324.1 When required. An automatic sprinkler system shall be installed throughout every dwelling in accordance with NFPA 13D, when any of the following conditions are present:
    1. the structure is over two stories high, as defined by the building code;
    2. the nearest point of structure is more than 150 feet from the public way;
    3. the total floor area of all stories is over 5,000 square feet (excluding from the calculation the area of the basement and/or garage); or
    4. the structure is located on a street constructed after March 1, 2000 that has a gradient over 12% and, during fire department response, access to the structure will be gained by using such street. (If the access is intended to be from a direction where the steep gradient is not used, as determined by the Chief, this criteria shall not apply).
    R324.2 Installation requirements and standards. Such sprinkler system shall be installed in basements, but need not be installed in garages, under eves or in enclosed attic spaces, unless required by the Chief. Such system shall be installed in accordance with NFPA 13D."
    (2) In IRC, Chapter 44, the following NFPA referenced standards are added as follows:
    "TABLE
    ADD
    13D-07Installation of Sprinkler Systems in One- and Two-family Dwellings and Manufactured Homes, as amended by these rules
    13R-07Installation of Sprinkler Systems in Residential Occupancies Up to and Including Four Stories in Height"
    (3) In NFPA, Section 13D-07, new sections are added as follows: "1.15 Reference to NFPA 13D. All references to NFPA 13D in the codes, ordinances, rules, or regulations governing NFPA 13D systems shall be read to refer to "modified NFPA 13D" to reference the NFPA 13D as amended by additional regulations adopted by Farmington City.
    4.9 Testing and Inspection of Systems. Testing and inspection of sprinkler systems shall include, but are not limited to:
    Residential:
    ROUGH Inspection-Verify Water Supply Piping Size and Materials, Installation of Riser, System Piping, Head Locations and all Components, Hydrostatic Pressure Test.
    FINAL Inspection-Inspectors Test Flow, System Completeness, Spare Parts, Labeling of Components and Signage, Alarm Function, Water Supply Pressure Verification.
    5.2.2.3 Exposed Piping of Metal. Exposed Sprinkler Piping material in rooms of dwellings shall be of Metal.
    EXCEPTIONS:
    a. CPVC Piping is allowed in unfinished mechanical and storage rooms only when specifically listed for the application as installed.
    b. CPVC Piping is allowed in finished, occupied rooms used for sports courts or similar uses only when the ceiling/floor framing above is constructed entirely of non-combustible materials, such as a concrete garage floor on metal decking.
    5.2.2.4 Water Supply Piping Material. Water Supply Piping from where the water line enters the dwelling adjacent to and inside the foundation to the fire sprinkler contractor point-of-connection shall be metal, suitable for potable plumbing systems. See Section 7.1.4 for valve prohibition in such piping. Piping down stream from the point-of-connection used in the fire sprinkler system, including the riser, shall conform to NFPA 13D standards.
    5.4 Fire Pump Disconnect Signs. When installing a Fire Pump, Red Plastic Laminate Signs shall be installed in the electrical service panel, if the pump is wired separately from the main disconnect. These signs shall state: "Fire Pump Disconnect ONLY" and "Main Breaker DOES NOT Shut Off Fire Pump".
    7.1.4 Valve Prohibition. NFPA 13D, Section 7.1 is hereby modified such that NO VALVE is permitted from the City Water Meter to the Fire Sprinkler Riser Control.
    7.6.1 Mandatory Exterior Alarm. Every dwelling that has a fire sprinkler system shall have an exterior alarm, installed in an approved location. The alarm shall be of the combination horn/strobe or electric bell/strobe type, approved for outdoor use.
    8.1.05 Plan Preparation Identification. All plans for fire sprinkler systems, except for manufacturer's cut sheets of equipment, shall include the full name of the person who prepared the drawings. When the drawings are prepared by a registered professional engineer, the engineer's signature shall also be included.
    8.7 Verification of Water Supply:
    8.7.1 Fire Flow Tests: Fire Flow Tests for verification of Water Supply shall be conducted and witnesses for all applications other than residential, unless directed otherwise by the Chief. For residential Water Supply, verification shall be determined by administrative procedure.
    8.7.2 Accurate and Verifiable Criteria. The design calculations and criteria shall include an accurate and verifiable Water Supply.
Enacted by Chapter 14, 2011 General Session